IMPORTANTREAD ALL OF THE FOLLOWINGWARNINGS AND STATEMENTSBEFORE READING THEINSTALLATION INSTRUCTIONSWARNINGLIQUEFIED PETROLEUM (L.P.)PROPANE GAS-FIRED
VICTORY VSPH Models10VICTORY VSPH MODELS- NON- DIRECT VENT, VENTING THROUGH A ROOFAll joints must be liquid and pressure tight. Use U/L listed single
VICTORY VSPH Models11VICTORY VSPH MODELS- NON - DIRECT VENT, UTILIZING AN EXISTING CHIMNEY AS A CHASEAll joints must be liquid and pressure tight. Use
VICTORY VSPH Models12VICTORY VSPH MODELS - DIRECT VENT, SIDEWALL VENTINGAll joints must be liquid and pressure tight. Use U/L listed single wall 3&quo
VICTORY VSPH Models13Figure 11. Vent/Air Intake Termination10. From inside, install inside termination plate using 4 screws. Make sure the 4" col
VICTORY VSPH Models14Figure 12. Direct vent, venting and air intake through a roof.VICTORY VSPH MODELS DIRECT VENT, VENTING AND AIR INTAKE THROUGH A R
VICTORY VSPH Models15VENTING AND AIR INTAKE SYSTEM REGULAR INSPECTIONA. Inspect the system regularly for condensation, corrosionand/or physical damag
VICTORY VSPH Models16PILOT PILOT BURNERBURNERMODEL UT-1107MODEL UT-1107P5P5P4P4P1P1P6P6P2P2P3P3INTEGRATED BOILER CONTROLINTEGRATED BOILER CONTROLFigur
VICTORY VSPH Models172. Power ConnectionA. Remove electrical junction box cover.B. Hot connection lead is black. Neutral connection lead is white.Prop
VICTORY VSPH Models18SETTING THE HIGH LIMITThe high limit is factory set at 190°F. To adjust, turn the HI LIMITDial Ato the desired setting. (Setting
VICTORY VSPH Models19uHIGH TEMP Illuminateswhen the boiler water tempera-ture reaches the high limit set-ting. It will remain lit until thewater tempe
VICTORY VSPH Models2NOTE: Height dimensions increase by11⁄2" and depth increases to 281⁄2" whencombustible floor kit is used.Natural #49 50
VICTORY VSPH Models20MULTIZONING OF VSPH BOILERZONE VALVE SYSTEM USING V8043E/F ZONE VALVESFigure 14.Figure 15.Figure 16.
VICTORY VSPH Models214. Air control system Diaphragm type compression tank is used to control system pressure. It must be installed at the boiler or b
VICTORY VSPH Models22II. Initial StartSafe lighting and other performance criteria were met whentesting various gas manifold and control assemblies us
VICTORY VSPH Models23a. Input for PROPANE is approximately at rating shown on ating plate when manifold pressure is 9-1⁄2" water columnb. Input
VICTORY VSPH Models24To reset the lockout condition: Turn down thermostat or turnpower off at disconnect switch for at least 45 seconds, thenrestore p
VICTORY VSPH Models25THERMOSTAT CALLS FOR HEATCIRCULATOR ONINDUCER (BLOWER) ONVSPH BOILER SEQUENCE OF OPERATIONBOILER WATER TEMPERATURE ISBELOW HIGH L
VICTORY VSPH Models26CARE AND MAINTENANCEThis section must be brought to the attention of the owner bythe installer so that the owner can make the nec
VICTORY VSPH Models27General Troubleshooting Guide For Service PersonnelTOP JACKETTOP JACKETFLUE COLLECTORFLUE COLLECTORINDUCERINDUCERBRUSHBRUSHWARNIN
VICTORY VSPH Models28CAUSE8. Defective pressure switch. POWER and PRES SWITCH LED’s flashing9. Defective high limit control10. Defective inducer motor
VICTORY VSPH Models29D. BURNER SHORT CYCLESCAUSE1. Thermostat heat anticipator set too low.2. Excessive pressure drop due to excess venting or air int
VICTORY VSPH Models3LOCATION AND IDENTIFICATION OF PARTSFigure 2. Location and identification of partsFigure 2a. Hydrolevel Model 3000 BoilerWater Tem
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600FAX: (516) 484-5921 • Canada: Slant/Fin LT D/LT EE, Mississauga, Ontariowww.slantf
VICTORY VSPH Models4The installation must conform to the requirements of theauthority having jurisdiction or, in the absence of suchrequirements, to t
VENTING APPLICATIONVSPH Series are sealed combustion type boilers, they maybeinstalled and vented either as a direct vent boiler which all airfor comb
When joining the various components of the above listedvent systems, the manufacturers’ instructions should beclosely followed to insure proper sealin
VICTORY VSPH Models7Maximum allowed flue and air intake equivalent length (Feet)forHeat-Fab Saf-T vent system (Including EZ Seal)Boiler ModelNumberPip
VICTORY VSPH Models8VENTING INSTALLATIONFollow the vent material manufacturer’s instructions in con-junction with these instructions for venting syste
VICTORY VSPH Models9VICTORY VSPH MODELS NON - DIRECT VENT, SIDEWALL VENTINGAll joints must be liquid and pressure tight. Use U/L listed single wall 3&