IMPORTANT
READ ALL OF THE FOLLOWING
WARNINGS AND STATEMENTS
BEFORE READING THE
INSTALLATION INSTRUCTIONS
WARNING
LIQUEFIED PETROLEUM (L.P.)
PROPANE GAS-FIRED BOILERS
Installation location ONLY as permitted in paragraph
entitled "LIQUEFIED PETROLEUM (L.P.) PROPANE
GAS-FIRED BOILER LOCATION" on page 4 of this
instruction book.
The above warning does not apply to NATURAL gas-
fired boilers.
The installation must conform to the requirements of
the authority having jurisdiction or, in the absence of
such requirements, to the National Fuel Gas Code,
ANSI Z223.1-latest edition. The installation must also
conform to the additional requirements in this Slant/Fin
Instruction Book.
In addition where required by the authority having juris-
diction, the installation must conform to American
Society of Mechanical Engineers Safety Code for
Controls and Safety Devices for Automatically Fired
Boilers, No. CSD-1.
WARNING
This boiler, gas piping and accessories must be
installed, connected, serviced and repaired by a
trained, experienced service technician, familiar with all
precautions required for gas-fired equipment and
licensed or otherwise qualified, in compliance with the
authority having jurisdiction.
WARNING
The venting system of this boiler is under positive pressure.
Leakage from this system can be hazardous and if not
avoided can result in death or serious injury. In addition to
the recommendations within this manual and the User’s
Information Manual, the venting system, from the blower to
the outdoor discharge, must be carefully checked annually
by a qualified service agency.
This manual must be left
with owner and should be
hung on or adjacent to
the boiler for reference.
VICTORY VSPH
INSTALLATION AND OPERATING INSTRUCTIONS
Printed in U.S.A. 413 Part No. 455056 Publication No. VSPH-41 Rev.A
Heating Contractor
Address
Phone Number
Boiler Model Number
Boiler Serial Number
Installation Date
DIRECT-VENT SEALED COMBUSTION BOILERS
HOT WATER MODELS VSPH-60 THROUGH VSPH-180
GAS-FIRED CAST-IRON BOILERS FOR NATURAL AND L.P. PROPANE GASES
TABLE OF CONTENTS
Dimensions, Rating and Orifice Sizes ........................................2
Identification of Parts..................................................................3
Installation Requirements ...........................................................4
Venting Application .....................................................................5
Boiler Room Air Supply and Ventilation......................................5
Flue gas Venting Requirements..................................................5
Vent Material ..............................................................................5
Air Intake Material ......................................................................6
Flue and Air Intake Restrictions .................................................6
Non-Direct Vent Installation ........................................................8
Sidewall Venting, Non-Direct Vent ..............................................8
Vent Termination Location and Clearance..................................8
Non-Direct Vent Vertical Venting.................................................8
Direct Vent Installation ................................................................8
Sidewall Venting, Direct Vent ......................................................8
Vent/Air Intake Termination Installation.......................................8
Direct Vent, Venting and Air Intake through a Roof..................13
Venting and Air Intake Regular Inspection ...............................15
Gas Piping ................................................................................15
Electrical Wiring........................................................................15
Boiler Water Temperature Control .......................................18-19
Multi Zoning ..............................................................................19
Indirect Water Heater Connections...........................................19
Water Piping .............................................................................19
Operating Instructions...............................................................21
Gas Input Rate Adjustment ......................................................22
Boiler Control............................................................................23
Status of Indicator Lights (LED’s) .............................................23
Safety Check ...........................................................................24
Sequence of Operation.............................................................25
Care and Maintenance .............................................................26
General Troubleshooting Guide...........................................27-29
Vedere la pagina 0
1 2 3 4 5 6 ... 29 30

Sommario

Pagina 1 - VICTORY VSPH

IMPORTANTREAD ALL OF THE FOLLOWINGWARNINGS AND STATEMENTSBEFORE READING THEINSTALLATION INSTRUCTIONSWARNINGLIQUEFIED PETROLEUM (L.P.)PROPANE GAS-FIRED

Pagina 2 - RATINGS AND DIMENSIONS

VICTORY VSPH Models10VICTORY VSPH MODELS- NON- DIRECT VENT, VENTING THROUGH A ROOFAll joints must be liquid and pressure tight. Use U/L listed single

Pagina 3

VICTORY VSPH Models11VICTORY VSPH MODELS- NON - DIRECT VENT, UTILIZING AN EXISTING CHIMNEY AS A CHASEAll joints must be liquid and pressure tight. Use

Pagina 4

VICTORY VSPH Models12VICTORY VSPH MODELS - DIRECT VENT, SIDEWALL VENTINGAll joints must be liquid and pressure tight. Use U/L listed single wall 3&quo

Pagina 5

VICTORY VSPH Models13Figure 11. Vent/Air Intake Termination10. From inside, install inside termination plate using 4 screws. Make sure the 4" col

Pagina 6

VICTORY VSPH Models14Figure 12. Direct vent, venting and air intake through a roof.VICTORY VSPH MODELS DIRECT VENT, VENTING AND AIR INTAKE THROUGH A R

Pagina 7

VICTORY VSPH Models15VENTING AND AIR INTAKE SYSTEM REGULAR INSPECTIONA. Inspect the system regularly for condensation, corrosionand/or physical damag

Pagina 8

VICTORY VSPH Models16PILOT PILOT BURNERBURNERMODEL UT-1107MODEL UT-1107P5P5P4P4P1P1P6P6P2P2P3P3INTEGRATED BOILER CONTROLINTEGRATED BOILER CONTROLFigur

Pagina 9

VICTORY VSPH Models172. Power ConnectionA. Remove electrical junction box cover.B. Hot connection lead is black. Neutral connection lead is white.Prop

Pagina 10 - VICTORY VSPH Models

VICTORY VSPH Models18SETTING THE HIGH LIMITThe high limit is factory set at 190°F. To adjust, turn the HI LIMITDial Ato the desired setting. (Setting

Pagina 11 - CHIMNEY AS A CHASE

VICTORY VSPH Models19uHIGH TEMP Illuminateswhen the boiler water tempera-ture reaches the high limit set-ting. It will remain lit until thewater tempe

Pagina 12

VICTORY VSPH Models2NOTE: Height dimensions increase by11⁄2" and depth increases to 281⁄2" whencombustible floor kit is used.Natural #49 50

Pagina 13

VICTORY VSPH Models20MULTIZONING OF VSPH BOILERZONE VALVE SYSTEM USING V8043E/F ZONE VALVESFigure 14.Figure 15.Figure 16.

Pagina 14 - VICTORY VSPH MODELS

VICTORY VSPH Models214. Air control system Diaphragm type compression tank is used to control system pressure. It must be installed at the boiler or b

Pagina 15

VICTORY VSPH Models22II. Initial StartSafe lighting and other performance criteria were met whentesting various gas manifold and control assemblies us

Pagina 16 - Figure 13b. Boiler control

VICTORY VSPH Models23a. Input for PROPANE is approximately at rating shown on ating plate when manifold pressure is 9-1⁄2" water columnb. Input

Pagina 17

VICTORY VSPH Models24To reset the lockout condition: Turn down thermostat or turnpower off at disconnect switch for at least 45 seconds, thenrestore p

Pagina 18 - IMPORTANT NOTICE

VICTORY VSPH Models25THERMOSTAT CALLS FOR HEATCIRCULATOR ONINDUCER (BLOWER) ONVSPH BOILER SEQUENCE OF OPERATIONBOILER WATER TEMPERATURE ISBELOW HIGH L

Pagina 19

VICTORY VSPH Models26CARE AND MAINTENANCEThis section must be brought to the attention of the owner bythe installer so that the owner can make the nec

Pagina 20 - MULTIZONING OF VSPH BOILER

VICTORY VSPH Models27General Troubleshooting Guide For Service PersonnelTOP JACKETTOP JACKETFLUE COLLECTORFLUE COLLECTORINDUCERINDUCERBRUSHBRUSHWARNIN

Pagina 21

VICTORY VSPH Models28CAUSE8. Defective pressure switch. POWER and PRES SWITCH LED’s flashing9. Defective high limit control10. Defective inducer motor

Pagina 22 - FIGURE 19

VICTORY VSPH Models29D. BURNER SHORT CYCLESCAUSE1. Thermostat heat anticipator set too low.2. Excessive pressure drop due to excess venting or air int

Pagina 23 - O = LED off = LED steady on

VICTORY VSPH Models3LOCATION AND IDENTIFICATION OF PARTSFigure 2. Location and identification of partsFigure 2a. Hydrolevel Model 3000 BoilerWater Tem

Pagina 24 - Power LED (Green)

SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600FAX: (516) 484-5921 • Canada: Slant/Fin LT D/LT EE, Mississauga, Ontariowww.slantf

Pagina 25

VICTORY VSPH Models4The installation must conform to the requirements of theauthority having jurisdiction or, in the absence of suchrequirements, to t

Pagina 26

VENTING APPLICATIONVSPH Series are sealed combustion type boilers, they maybeinstalled and vented either as a direct vent boiler which all airfor comb

Pagina 27

When joining the various components of the above listedvent systems, the manufacturers’ instructions should beclosely followed to insure proper sealin

Pagina 28

VICTORY VSPH Models7Maximum allowed flue and air intake equivalent length (Feet)forHeat-Fab Saf-T vent system (Including EZ Seal)Boiler ModelNumberPip

Pagina 29

VICTORY VSPH Models8VENTING INSTALLATIONFollow the vent material manufacturer’s instructions in con-junction with these instructions for venting syste

Pagina 30

VICTORY VSPH Models9VICTORY VSPH MODELS NON - DIRECT VENT, SIDEWALL VENTINGAll joints must be liquid and pressure tight. Use U/L listed single wall 3&