Section 5Electrical System
5-2
Refrigerators - Remote - RR1, RR2, RR3
For wiring diagram, see page 5-8
COOLING CYCLE
With the main ON/OFF switch in the ON
position, the current flows, energizing the
evaporator fan motors.
Current also flows through the closed contacts
of the temperature control, energizing the
liquid line solenoid valve. The increase in
suction pressure causes the contacts on the
low pressure switch to close, energizing the
refrigeration system.
OFF CYCLE
When the temperature control senses the
proper temperature, it opens, shutting off the
liquid line solenoid valve. The drop in suction
pressure causes the low pressure switch to
open, de-energizing the refrigeration system.
The refrigeration system remains off until the
temperature control senses approximately
38°F (3.3°C). (This also keeps the evaporator
defrosted.) At that time, the temperature
control closes and starts the refrigeration
system.
Freezers - Self-Contained - F1, F2, F3
For wiring diagram, see pages 5-9, 5-10, 5-11
COOLING CYCLE
With the main ON/OFF switch in the ON
position, the current flows, energizing the
automatic defrost time clock.
Current also flows through the closed contacts
of the temperature control, energizing the
condenser fan motor(s) and the compressor.
With contact N closed on the automatic
defrost time clock, current will flow through
the normally open (N.O.) light/fan switch
contacts (with the door closed).
When the evaporator coil temperature reaches
30 to 35°F (-1.1 to 1.7°C), the defrost end and
fan delay thermostat closes, energizing the
evaporator fans.
DEFROST CYCLE
At preset times on the automatic defrost time
clock, the contacts switch to defrost the
evaporator. Contact N opens, de-energizing
the evaporator fan motor(s). Contact #4
opens, de-energizing the refrigeration system.
Contact #1 closes, energizing the evaporator
defrost heater.
As the evaporator temperature rises, the
defrost end and fan delay thermostat opens to
terminate the defrost cycle. Contact #1 opens,
de-energizing the defrost heater. Contacts N
and #4 close, energizing the refrigeration
system.
OFF CYCLE
When the temperature control senses the
proper temperature, it opens, shutting off the
refrigeration system.