Section 6Refrigeration System
6-12
7. Attach a SUVA
â
HP81 conversion label
(Part #8134983) next to each serial
number plate and next to the service
valves or the front of the control box.
Figure 6-1: DuPont SUVA
â
ââ
â
HP81 Conversion Label
Important
Write the service company name and
conversion date on each label.
8. Start the Reach-In. Verify that it operates
properly.
HEAT EXCHANGER REMOVAL
(FS1 and FS2 models only)
CAUTION
Remove the entire system charge before
proceeding.
1. Remove the insulation from the suction
line liquid heat exchanger assembly. The
liquid line has been soldered to the suction
line for about 15” (38 cm).
2. Starting from the evaporator end, carefully
remove the liquid line from the suction
line. Use a pliers and a low flame torch.
3. Insulate the suction line. Run the removed
liquid line along the outside of the suction
line insulation.
Figure 6-2: Heat Exchanger Removal
IMPORTANT
This reach-in is converted to
DuPont Suva
â
ââ
â
HP81 (R402B)
Refrigerant
in accordance with Manitowoc guidelines.
REFRIGERANT CHARGE
The Suva
â
ââ
â
HP81 charge remains the same as
R-502 charge specified on the serial plate.
ELECTRICAL/PRESSURE RATINGS
All electrical and pressure ratings listed
on serial plate remain the same.
Service Co. _____________________________
Month _________________ Year ___________
Manitowoc Ice, Inc. 8134983
TO EXPANSION
VALVE
SV1538
SUCTION LINE
FROM
EVAPORATOR
FROM CONDENSER
LIQUID LINE
FILTER DRIER
DO NOT REINSULATE
AFTER UNSOLDERING
TO
COMPRESSOR
REINSULATE
AFTER
UNSOLDERING
REMOVE
(UNSOLDER ENTIRE
HEAT EXCHANGER
APPROX. 15”)