Section 6Refrigeration System
6-24
HFC REFRIGERANT
Manitowoc uses R-404A and R-134A HFC
refrigerants with ozone depletion potential
(ODP) factors of zero (0.0). R-404A is used in
Reach-In freezers and R-134A is used in
Reach-In refrigerators.
1. What compressor oil does Manitowoc
require for use with HFC refrigerants?
Manitowoc products use Polyol Ester (POE)
type compressor oil. It is the lubricant of
choice among compressor manufacturers.
2. What are some of the characteristics of
POE oils?
They are hygroscopic, which means they have
the ability to absorb moisture. POE oils
are 100 times more hygroscopic than
mineral oils. Once moisture is absorbed
into the oil, it is difficult to remove, even
with heat and vacuum. POE oils are also
excellent solvents, and tend to “solvent
clean” everything inside the system,
depositing material where it is not wanted.
3. What do these POE oil characteristics
mean to me?
You must be more exacting in your
procedures. Take utmost care to prevent
moisture from entering the refrigeration
system. Keep oil containers and
compressors capped at all times to
minimize moisture entry. Before removing
the system charge to replace a faulty
component, be sure you have all of the
needed components at the site.
Refrigeration systems and compressors
with POE oil should not be left open to
the atmosphere for more than 15
minutes.
Remove new system component plugs and
caps just prior to brazing. Be prepared to
connect a vacuum pump immediately after
brazing.
4. Are there any special procedures required
if a POE system is diagnosed with a
refrigerant leak?
For systems found with positive refrigerant
system pressure, no special procedures are
required.
For systems found without any positive
refrigerant pressure we will assume
moisture has entered the POE oil. After
the leak is found and repaired, the
compressor oil must be changed. The
compressor must be removed and at least
95% of the oil drained from the suction
port of the compressor. Use a “measuring
cup” to replace the old oil with exactly the
same amount of new POE oil such as
Mobil EAL22A. Remember, care must be
taken to prevent moisture from getting
into the refrigeration system during
refrigeration repairs.
5. How do I leak-check a system containing
HFC refrigerant?
Use equipment designed for HFC detection.
Do not use equipment designed for CFC
detection. Consult leak detection
equipment manufacturers for their
recommendations. Also, standard soap
bubbles will work with HFC refrigerants.
6. Does Manitowoc use a special liquid line
filter-drier with HFC refrigerants?
Yes. Manitowoc uses an ALCO “UK” series
filter-drier for increased filtration and
moisture removal. During a repair,
Manitowoc recommends installing the
drier just before hooking up a vacuum
pump.