Section 7Diagnostics
7-10
Mullion (Door Frame) Heater Switch
(Refrigerator Only)
NOTE: On a freezer, the door heater wire is
connected directly to the power supply. It will
be on any time the main power supply switch
is on.
FUNCTION
Energizes mullion heaters to prevent
condensation (sweating) on cabinet and door
surfaces.
SPECIFICATIONS
Single pole single throw (SPST)
CHECK PROCEDURES
1. Check for proper line voltage (+/- 10%).
2. Inspect the switch for proper wiring.
3. Inspect the terminals for clean, tight
connections.
4. Check across the switch terminals with a
voltmeter. Replace the switch if you do
not obtain the results below:
Switch Position Voltage
On 0
Off line
Drain Tube Heater (Freezer Only)
FUNCTION
Prevents frost and ice from accumulating in
the drain tube.
SPECIFICATIONS*
Heater Type Ohm Reading
10 Watt/120 Volt 1200 - 1343
10 Watt/240 Volt 5400 - 6600
*Listed ohm values are at 77°F (25°C).
CHECK PROCEDURES
1. Turn off the electric power to the reach-in
freezer.
2. Disconnect the leads to the drain tube
heater. Check with an ohmmeter. See
Specifications (above) for ohm values.
Results of Check Action
Continuity
and ohm value
within specifications
Heater is OK
No continuity Replace the heater
Ohm value not
within specifications
Replace the heater
See page 8-5 for replacement procedures.
Condensate Vaporizer Pan
FUNCTION
Vaporizes evaporator condensate if a floor
drain is unavailable.
SPECIFICATIONS
120 volts, 1.3 amps
CHECKOUT PROCEDURES
1. Verify that power is supplied to the unit.
2. Check the heater amps. If the reading is
not as specified above, replace the heater.